Maxims and Instructions for the Boiler Room Useful to Engineers, Firemen & Mechanics; Relating to Steam Generators, Pumps, Appliances, Steam Heating, Practical Plumbing, etc.
The most important thing in connecting the relief to return pipes is, that it should always be carried down below the line, the same as all vertical return pipes. In connecting the reliefs, so that the lower opening can at any time be exposed to the steam, there will be the difficulty of having the steam going in one direction, and the water in another.
The relief pipe should “tap” the steam at its lowest or most depressed points. It should always be put in at the base of all steam “risers” taking steam to upper floors.
In leaving the boiler with main steam pipe, raise to a height that will allow of one inch fall from the boiler to every ten feet of running steam pipe; this is sufficient, and a greater fall or pitch will cause the condensed water in the pipe to make at times a disagreeable noise or “gurgling.”
The flow pipe should never start from the boiler in a horizontal direction, as this will cause delay and trouble in the circulation. This pipe should always start in a vertical direction, even if it has to proceed horizontally within a short distance from the boiler. Reflection will show that the perfect apparatus is one that carries the flow pipe in a direct vertical line to the cylinder or tank; this is never, or but rarely possible, but skill and ingenuity should be exercised to carry the pipes as nearly as possible in this direction.
The flow of steam ought not to be fast enough to prevent the water of condensation from returning freely. All the circulating pipes should be lowest at the discharge end, and the inclination given them should not be less than one foot in fifty.
The general rule is to lay the main pipes from the boiler so that the pipe will drain from the boiler. Where this is done it is necessary to have a drip just before the steam enters the circulation. This drip is connected to a trap, or, if the condensed water is returned to the boiler, the drip is arranged accordingly.
But it is the best practice to lay the main pipe with the lowest part at the boiler, so that the drip will take care of itself, and not require an extra trap, nor interfere with the return circulation.
When steam is turned into cold pipes the water of condensation gets cold after running a short distance, and if it has to go through a small drip pipe full of frost it will probably be frozen. Then, unless it is followed up with a pail of hot water, the whole arrangement will be frozen and a great many bursted pipes will result. Whenever turning steam on in a system of very cold pipes, only one room should be taken at a time, and a pail of hot water should be handy so that if the pipe becomes obstructed it can be thawed immediately without damage.
When pipes become extensively frozen there is nothing to do but take them out and put in new ones.
The manner in which a temperature too low to start rapid combustion in wood in steam pipes, operates in originating a fire is by first reducing the oxide of iron (rust) to a metallic condition. This is possible only under certain external conditions, among them a dry atmosphere. Just as soon as the air is recharged with moisture, the reduced iron is liable to regain, at a bound, its lost oxygen, and in doing so become red hot. This is the heat that sets the already tindered wood or paper ablaze.
Where there is no rust there is no danger from fire with a less than scorching temperature in the pipe or flue. Hence the necessity of keeping steam or hot water fittings in good order.
The indirect system of heating is the most expensive to put in; as to the cost of providing nearly double the heating surface in the coils must be added the cost of suitable air boxes, pipes and registers. For a large installation, this is a serious matter, although for office warming the advantages gained on the score of healthfulness and greater efficiency of employees much more than counterbalance the extra expense.
One horse power of boiler will approximately heat 6,000 to 10,000 cubic feet in shops, mills and factories—dwellings require only one horse power for from 10,000 to 20,000 cubic feet.
From seven to ten square feet of radiating surface can be heated from one square foot of boiler surface, i.e., the heating surface of the boiler and each horse power of boiler will heat 240 to 360 feet of 1-inch pipe.
The profession most nearly related to that of steam engineers is the working steam fitters’ occupation. Strictly speaking, the engineer should produce the steam, and it is the steam fitters’ place to fix up all the steam pipes and make all the necessary connections: but where the steam plants are small, the engineer may be steam fitter also: hence the introduction in this work of these “Points” which are necessary to be known for the proper care and management of any system of steam or hot water heating.
The care and patience, the mental strain and not infrequently the physical torture incident to fitting up a complicated pipe system cannot adequately be set forth in words.
It is stated to be a fact, that in high pressure hot water heating the water frequently becomes red hot, pressures of 1000 to 1200 pounds per square inch being reached, and when the circulation of the system is defective the pipe becomes visibly red in the dark.
Pipes under work benches should be avoided, unless there is an opening at the back to permit the escape of the heated air, which would otherwise come out at the front.
When both exhaust and live steam are used for heating, many engineers prefer to use independent lines of pipe for each, rather than run the risk of interference and waste caused by admitting exhaust and live steam into the same system at the same time. Nevertheless, the advantages gained by being able to increase the heating power of a system in extremely cold weather by utilizing the entire radiating surface for high pressure steam, are so great that it is probably better so to arrange the system of pipes and connections that this can be done.
Double extra heavy pipe (XX) is used for ice and refrigerating machines (see page 246), as a general rule, makers of this class of machinery obtain but little satisfaction in the use of the ordinary thread joining and use special dies with uniform taper—both for couplings, flanges and threading the pipe itself. They do this to protect their reputation and guarantees.
Welding boiler and other tubes.—The following is a good way in cases of emergency and can be done on a common forge:
Enlarge one end of the shortest piece, and one end of the long piece make smaller, then telescope the two about 3⁄4 of an inch. Next get an iron shaft as large as will go into the tube and lay across the forge with the tube slipped over it. Block the shaft up so that the tube will hang down from the top of the shaft. By such an arrangement the inside of the tube will be smooth for a scraper. When the tube gets to a welding heat strike on the end of the short piece first, with a heavy hammer, then with a light and broad-faced hammer make the weld. Borax can be used to good advantage, but it is not necessary. The next thing is to test the tube, which can be done in the following manner: Drive a plug in one end of the tube, stand it up on that end, and fill it with water, if it does not leak the job is well done, if a leak exists the welding must be again done.
Solid-drawn Iron Tubes: Calculated Bursting and Collapsing Pressures.
| External Diameter. | Thickness. | Internal Diameter. | Bursting Pressure. | Collapsing Pressure. | ||
|---|---|---|---|---|---|---|
| Per Square Inch of Internal Surface. | Per Square Inch of Section of Metal. | Per Square Inch of External Surface. | Per Square Inch of Section of Metal. | |||
| Inches. | Inch. | Inches. | Lbs. | Tons. | Lbs. | Tons. |
| 11⁄4 | .083 | 1.084 | 7700 | 22.4 | 6500 | 21.7 |
| 13⁄8 | .083 | 1.209 | 6900 | 22.4 | 5800 | 21.3 |
| 11⁄2 | .083 | 1.334 | 6200 | 22.4 | 5200 | 21.0 |
| 13⁄4 | .083 | 1.584 | 5300 | 22.4 | 4300 | 20.3 |
| 2 | .083 | 1.834 | 4500 | 22.4 | 3700 | 19.7 |
| 21⁄4 | .095 | 2.060 | 4600 | 22.4 | 3600 | 19.0 |
| 21⁄2 | .109 | 2.282 | 4800 | 22.4 | 3600 | 18.3 |
| 23⁄4 | .109 | 2.532 | 4400 | 22.4 | 3100 | 17.7 |
| 3 | .120 | 2.760 | 4300 | 22.4 | 3000 | 17.0 |
| 31⁄2 | .134 | 3.232 | 4200 | 22.4 | 2700 | 15.7 |
| 33⁄4 | .134 | 3.482 | 3900 | 22.4 | 2400 | 15.0 |
| 4 | .134 | 3.732 | 3600 | 22.4 | 2100 | 14.3 |
| 41⁄2 | .134 | 4.232 | 3200 | 22.4 | 1700 | 13.0 |
| 43⁄4 | .134 | 4.482 | 3000 | 22.4 | 1600 | 12.3 |
| 5 | .134 | 4.732 | 2800 | 22.4 | 1400 | 11.7 |
| 51⁄2 | .148 | 5.204 | 2800 | 22.4 | 1200 | 10.3 |
| 6 | 5.704 | 2600 | 22.4 | 1000 | 9.0 | |
VENTILATION.
The quantity of air for each minute for one person is from four to fifteen feet—and from one-half to one foot should be allowed for each gas jet or lamp.
Heated air cannot be made to enter a room unless means are provided for permitting an equal quantity to escape, and the best places for such exit openings is near the floor.
For healthful ventilation the indirect system of steam heating is by far the best yet devised, for it not only warms the room, but insures perfect ventilation as well. In this system, the air for warming the room is introduced through registers, having first been heated by passing over coils of pipe or radiators suitably located in the air ducts. There is a large volume of pure air constantly entering the room, which must displace and drive out an equal quantity of impure air. This escapes principally around the doors and windows, so that not only is the ventilation effected automatically without the use of special devices, but all disagreeable indraft of cold air is prevented.
One of the cheapest and best methods of ventilation is to have an opening near the floor, opening directly into the flue, or some other outlet especially constructed for it, with hot water or steam pipes in this opening. A moderate degree of heat in these pipes will create a draft, and draw out the bad air. Only a few of these pipes are necessary, and the amount of hot water or steam required to heat them is too small to be worthy of consideration.
The use of a small gas-jet, burning continuously, in a pipe or shaft has been found to be a most admirable method of ventilating inside rooms, closets and similar places where foul air might collect if not replaced by fresh. The following table exhibits the result of careful experiments made by Mr. Thomas Fletcher, of England, with a vertical flue 6 inches in diameter and 12 feet high:
Table.
| Gas Burnt per Hour. | Speed of Current per Minute. | Total Air Exhausted per Hour. | Air Exhausted per Cubic foot of Gas Burnt. | Temperature at outlet. Normal 62° Fahr. |
|---|---|---|---|---|
| Cubic Feet. | Feet. | Cubic Feet. | Cubic Feet. | |
| 1 | 205 | 2,460 | 2,460 | 82° |
| 2 | 245 | 2,940 | 1,470 | 92° |
| 4 | 325 | 3,900 | 975 | 110° |
| 8 | 415 | 4,980 | 622 | 137° |