Maxims and Instructions for the Boiler Room Useful to Engineers, Firemen & Mechanics; Relating to Steam Generators, Pumps, Appliances, Steam Heating, Practical Plumbing, etc.
Fig. 36 (page 84) shows the boiler sectionally, over the bridge wall; the shaded tube ends exhibit the cluster which return the heat products to the rear of the boiler, after being brought forward by the two outer clusters which are left unshaded.
This arrangement of the tubes gives several advantages:
1. It enables an exceedingly high furnace temperature, without loss at the chimney.
2. By dividing the heat into these currents a more equal expansion and contraction is secured. This is an important point secured.
3. In this system the tubes are almost equally operative.
4. The extra body of water immediately over the furnace is both an element of safety and a reservoir of power.
5. The outlet for the waste products of combustion is found in this style of boiler in a more convenient position at the rear end of the boiler.
6. The boiler being self-contained, can be used in places where height of story is limited.
SPECIFICATION FOR 125 HORSE POWER BOILER.
For one Horizontal Tubular Boiler 72 inches diameter 18 feet long for…………………of………
Type.
The boiler to be of the Horizontal Tubular type with all castings and mountings complete.
Dimensions.
Boiler 72 inches diameter and 18 feet long. Each boiler to contain 90 best lap welded tubes 31⁄2 inches diameter by 18 feet long, set in vertical and horizontal rows with a space between them vertically and horizontally of no less than one inch and one-quarter (11⁄4) except central vertical space, which is to be three inches (3). No tube to be nearer than two and one-half inches (21⁄2) to shell or boiler. Holes through heads to be neatly chamfered off. All tubes to be set by Dudgeon Expander and slightly flared at front end, turned over and beaded down at back end.
Quality and Thickness of Steel Plates.
Shell plates to be 1⁄2-inch thick of homogeneous steel of uniform quality having a tensile strength of not less than 65,000 lbs. Name of maker, brand and tensile strength to be plainly stamped on each plate.
Heads to be of same quality as plates of shell in all particulars 3⁄4-inch thick. Bottom of shell to be of one plate, and no plate to be less than 7 feet wide. Top of shell to be in three plates. All plates planed before rolling, and all joints fullered not caulked.
Flanges.
All flanges to be turned in a neat manner to an internal radius of not less than two inches (2) and to be clear of cracks, checks or flaws.
Riveting.
Boilers to be riveted with 3⁄4-inch rivet throughout. All girth seams to be double riveted. All horizontal seams to be double riveted. Rivet holes to be punched or drilled so as to come fair in construction. No drift pins to be used in construction of the boilers.
Braces.
All braces to be of the crowfoot pattern, one and one eighth (11⁄8) inch diameter and the shortest to be no less than four feet (4) long and of sufficient number for thorough bracing, and to bear uniform tension.
Manholes, Hand Holes and Thimbles.
One manhole in top of each boiler with heavy cast iron frame riveted on middle of centre plate; one manhole near the bottom of each front head; head reinforced with a wrought iron ring two inches (2) square, riveted to heads with flush countersunk rivets two inches (2) pitch and to have all the necessary bolts, plates, guards and gaskets; two six-inch thimbles riveted to top of each boiler, each to have a planed face; one heavy 6-inch flange on bottom of each boiler, 12 inches from back end to centre of flange. There must be two braces, one on each side of manhole in front head; also to have three braces opposite manhole on back head below tubes.
Lugs.
Four (4) lugs riveted on each side of boilers, of good and sufficient size, with six one-inch rivets in each lug.
Castings.
Each boiler to have a complete set of castings consisting of ornamental flush fronts containing tube, fire and ash-pit doors, and provide the best stationary grate bars as may be selected by buyer, with the necessary fixtures, all bearing bars, britching plates, dead plates, binder bars, back cleaning out doors with frames. Anchor bolts and buck stays. The fire door to contain adjustable air opening and to be protected with fire shields. One heavy cast iron arch over each boiler.
Testing.
Boilers to be tested with a water pressure of 200 lbs. per square inch and certificate of such test having been made shall be furnished with boiler. Test of boiler to be under direction of such steam boiler Insurance Company as may be selected by buyer.
Quality and Workmanship.
All boilers to be made in the best workmanlike manner and all material of their respective kinds to be of the best, and in strict accordance with specification.
Fittings and Mountings.
The boiler to be furnished with the following: One four inch heavy mounted safety valve. One six inch flanged globe valve. Two two inch best globe valves. Two two inch check valves. One eight inch dial nickel plated steam gauge. One low water alarm gauge. One set of fire irons for two boilers consisting of hoe, poker, slice bar and shovel.
Drawings.
All drawings furnished for masons in setting the boilers.
Duty of Boiler.
The boiler to develop 120 horse power and to work under a constant pressure varying from 125 to 150 lbs. to the square inch.
All rivets are to be 21⁄2 and 11⁄2 inch pitch. The pitch line of the rivets to be not nearer 11⁄8 inches to the edge of the sheet.
To be 8 lug plates for each boiler not less than 2 feet long, 8 inches wide, and one inch thick.
There shall be six 1 inch anchor rods running front to rear of each boiler, in the brick work.
These boilers and all their fronts, fittings and connections will be subject to the inspection of…………………
MARKS ON BOILER PLATES.
Something has been said under another heading of the nature and requisite quality of the materials entering into the structure of the boiler. Too much emphasis cannot be laid upon the necessity for the use of the very best iron and steel that can be manufactured, and the most skillful and thorough workmanship that can be performed in constructing the boiler.
It is becoming the practice, both for land and marine boilers, for boiler plate makers to furnish “test pieces” from each sheet or plate that goes into the construction of a boiler, and a sheet showing the tensile strength of each sheet or plate that enters into its make up.
But irrespective of this practice each plate entering into boiler construction will be found to have one of the following marks, which designate its quality and method of manufacture. The name “Charcoal Iron” is used because in its manufacture wood charcoal is employed instead of mineral fuel.
“Charcoal No. 1 Iron” (C. No. 1) is made entirely of charcoal iron. It has a tenacity of 40,000 pounds per square inch in the direction of the fibre. It is hard, but not very ductile, and should never be used for flanging.
“Charcoal Hammered No. 1 Shell Iron” (C. H. No. 1 S.), although not necessarily hammered, has been worked up before it is rolled into plates. It has a tenacity of 50,000 to 55,000 pounds per square inch in the direction of the fibre. It is rather hard iron, and should not be flanged. It is used for the outside shell of boilers.
“Flange Iron” (C. H. No. 1 F.), is a ductile material which can be flanged in every direction. It has a tenacity of 50,000 to 55,000 pounds per square inch along the fibre.
“Fire Box Iron” (C. H. No. 1 F. B.), is a harder quality, designed especially to withstand the destructive effect of the impinging flame, and is used for boxes and flue-sheets.
The letters in the brackets exhibit the plate stamp.
Cast iron and copper were used in an early day for steam boilers and the former is still extensively used for certain forms of low pressure steam heaters made for various purposes, such as green houses, etc.
CONSTRUCTION OF BOILERS.
In selecting a boiler, the most efficient design will be found to be that in which the greatest amount of shell surface is exposed to direct heat. It is the direct heating surface that does the bulk of the work and every tendency to reduce it, either in the construction or setting of the boiler, should be avoided. The smaller the amount of surface enclosed by or in contact with the setting, the better results will be obtained.
A boiler with a bad circulation is the bane of an engineer’s existence. Proper circulation facilities constitute one of the chief factors in the construction of a successful and economical boiler. In tubular boilers the best practice places the tubes in vertical rows, leaving out what would be the centre row. The circulation is up the sides of the boiler and down the centre. Tubes set zig-zag to break spaces impede the circulation and are not considered productive of the best results.
The surface from which evaporation takes place should be made greater as the steam pressure is reduced, that is to say, as the size of the bubbles of steam become greater. To produce 100 lbs. of steam per hour at atmospheric pressure this surface should not be less than 732 square feet, which may be reduced to 146 square feet for steam at 75 lbs. pressure, and to 73 feet for steam at a pressure of 150 lbs. It is for this reason that triple-expansion engines can be worked with smaller boilers than are required with engines using steam of lower pressure. The amount of steam space to be permitted depends upon the volume of the cylinders and the number of revolutions made per minute. For ordinary engines it may be made a hundred times as great as the average volume of steam generated per second.
A volume of heated water in a boiler performs the same office in furnishing a steady supply of steam as a fly-wheel does to an engine in insuring uniformity of speed; hence the centre space of a boiler should be ample, in order to take advantage of this reserve force.
QUALITY OF STEEL PLATES.
Steel for boilers is always of the kind known as low steel, or soft steel, and is, properly speaking, ingot iron, all of its characteristics being those of a tenacious, bending, equal grained iron, and quite different from true steels, such as knife blades, cutting tools, etc., are composed of. Steel is rapidly displacing iron in boiler construction, as it has greater strength for the same thickness, than iron; and, except in rare instances, where the nature of the water available for feed renders steel undesirable, iron should not be used for making boilers, careful tests having shown it to be vastly inferior to steel in many important features.
Good boiler steel up to one-half inch in thickness should be capable of being doubled over and hammered down on itself without showing any signs of fracture, and above that thickness it should be capable of being bent around a mandrel of a diameter equal to one and one-half times the thickness of the plate, to an angle of 180 degrees without sign of distress. Such bending pieces should not be less in length than sixteen times the thickness of the plate.
On this test piece the metal should show the following physical qualities:
Tensile strength, 55,000 to 65,000 pounds per square inch.